Safety Gear Store are able to install, commission and service your fixed gas detection system. We offer a professional service from fully trained, certified and manufacturer approved engineers, we are also one of the only suppliers with engineers that carry spares in their vehicles to ensure a quick and efficient service that will enable you to continue using your facility.
For more information on what we offer please visit one of the below pages:
Fixed Gas Detection System Install and Commissioning
Fixed Gas Detection System Calibration and Servicing
| Gas Measured: | Carbon Monoxide (CO) |
| Part No.: | MIDAS-S-COX |
| Sensor Technology: | 3 electrode electrochemical cell |
| Measuring Range (ppm): | CO 0 – 100ppm |
| Minimum Alarm 1 Set Point: | 12.5ppm |
| Repeatability: | < ± 2% of measured value |
| Linearity: | < ± 2% of measured value |
| Response Time: | ≤ 60 seconds |
| Sensor Cartridge Life Expectancy: | ≥ 24 months under typical application conditions |
| Operating Temperature: | 0°C to +40°C (32°F to 104°F) |
|
Effect of Tempearture: Zero Sensitivity |
< ± 0.035ppm / °C < ± 0.8% of measured value / °C |
|
Operating Humidity (coninuous): Effect of Humidity Zero Sensitivty |
15 – 90% rH
< ± 0.02ppm of measured value / % rH No effect |
| Operating Pressure: | 70 – 110kPa |
| Effect of Position: | No effect in typical application |
|
Long Term Drift Zero Sensitivty |
< 2ppm / year < ± 5% of measured value / year |
| Calibration Gas: | Carbon Monoxide (CO) |
| Challenge Gas (Bump Test): | Carbon Monoxide (CO) |
| Warm Up Time: | < 10 minutes |
| Storage Temperature | +5°C to +25°C (+41°F to +77°F) |
| Attribute name | Attribute value |
|---|---|
| Gases Detected | Carbon Monoxide (CO) |