Don't have an account?
Require Install, Commissioning, Calibration or Servicing?
Safety Gear Store are able to install, commission and service your fixed gas detection system. We offer a professional service from fully trained, certified and manufacturer approved engineers, we are also one of the only suppliers with engineers that carry spares in their vehicles to ensure a quick and efficient service that will enable you to continue using your facility.
For more information on what we offer please visit one of the below pages:
Fixed Gas Detection System Install and Commissioning
Fixed Gas Detection System Calibration and Servicing
| Gas Measured: | Ammonia (NH3) |
| Part No.: | MIDAS-E-NH3 |
| Sensor Technology: | 3 electrode electrochemical cell |
| Measuring Range (ppm): | NH3 0 – 100ppm |
| Minimum Alarm 1 Set Point: | 12.5ppm |
| Repeatability: | < ± 5% of measured value |
| Linearity: | < ± 2% of measured value |
| Response Time: | < 10 seconds |
| Sensor Cartridge Life Expectancy: | ≥ 24 months under typical application conditions |
|
Operating Temperature: Effect of Temperature: Zero Sensitivity |
0°C to +40°C (32°F to 104°F) < ± 0.1ppm / °C < ± 1% of measured value / °C (0°C to 25°C) < ± 0.2% of measured value / °C (25°C to 40°C) |
| Operating Humidity: | 15 – 90% rH |
| Operating Pressure: | 90 – 110kPa |
| Effect of Position: | No effect in typical application |
| Calibration Gas: | Ammonia (NH3) |
| Challenge Gas (Bump Test): | Ammonia (NH3) |
| Warm Up Time: | < 10 minutes |
| Attribute name | Attribute value |
|---|---|
| Gases Detected | Ammonia (NH3) |
Place a purchase order, call or email to get an international shipping quote
SECURED BY SECTIGO (We do not accept AMEX)
Call or email to speak to a member of the technical team