- Input voltage range: 16 to 32 VDC (24 VDC nominal)
- Communication: RS485, MODBUS RTU
- Certified temperature range: 40° to +149°F (-40° to +65°C)

Overiew
Sensepoint XCD now has remote monitoring capabilities for its toxic and Oxygen sensors. Its remote capability is designed to offer excellent flexibility of use and is an ideal solution for hard-to-reach locations or areas where the transmitter needs to be separate from the sensor. With remote toxic and Oxygen sensor mounting of up to 100 feet (30m) away from the transmitter, Sensepoint XCD provides a robust monitoring solution even in challenging environments where detection is difficult, including applications where the point of detection is in an area that is not easily accessible or where the detector would not be visible, like in high or low level concealed areas or outside a room being monitored.  

Sensepoint XCD is easy to use. The sensor simply plugs into the bottom of the transmitter and the transmitter automatically configures itself accordingly. Users can modify detector operation using the LCD and magnet switches without ever needing to open the unit. This enables one-man, non-intrusive operation and reduces routine maintenance time and costs.

A tri-color backlit LCD clearly indicates the unit’s status at a glance, even from a distance. A steady green backlight indicates normal operation, flashing yellow indicates fault and flashing red indicates an alarm.

All detectors are supplied pre-configured and include two programmable alarm relays, one programmable fault relay as well as an industry standard 4-20mA output (sink or source selectable) and MODBUS communication. The scale, range, relay operation, alarm set point and electronic tag number of the detector can be adjusted using the transmitter's LCD and non-intrusive magnetic switches. Outputs are automatically inhibited during adjustment, thereby reducing the risk of false alarm at the control panel during maintenance.

Additional Features and Benefits:

All-In-One Gas Monitoring Solution:
- Flammable (catalytic or infrared), toxic and oxygen versions available 
- Serves new/retrofit, indoor/outdoor applications 
- Stainless steel or aluminum explosion-proof housing options 
- IP66 as standard
- Proven and Reliable Sensor Technology

SurecellTM electrochemical sensors:
- Poison immune infrared sensors 
- Poison resistant catalytic bead sensors 
- Long life sensors
- Global Approvals
- US and Latin America, European, Canadian and Asian 
- Compliant with UL, INMETRO, ATEX,  IECEx, CSA, KTL, PA, GB and CCCF standards

Easy to Use: 
- User friendly and intuitive tri-color backlit display with digits, bar graph and icons 
- Fully configurable via magnetic switches 
- Optional remote sensor mounting 
- Selectable sink or source 4-20mA output 
- Auto-inhibit during maintenance 
- MODBUS communications for remote diagnostics/configuration

Cost Effective:
- Common transmitter platform 
- Minimal training required 
- Reduced spares 
- Non-intrusive, one-man operation 
- Plug-in sensor replacement 
- MODBUS multi drop option offers cabling savings

Simple Installation:
- Plug-in display module removes to give access to terminal area 
- Integral mounting bracket 
- 2 x M20 or ¾” NPT cable/conduit entries                     
- Removable plug/socket type terminal blocks for              
- Sink/source switch to suit preferred wiring topology 
- Integral mounting plate attaches to surface, horizontal or vertical piping

Options availabe are:

SPXCDASMFX

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes catalytic sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDASMRX

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes infrared methane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDASMPX

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes infrared propane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDASMO1

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes oxygen EC sensor cartridge 0 to 25% v/v, includes nylon weather protection

SPXCDASMHX

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes hydrogen sulfide EC sensor cartridge 0 to 50ppm, user selectable FSD between 10 and 100ppm (1 ppm resolution), includes nylon weather protection

SPXCDASMCX

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes carbon monoxide EC sensor cartridge 0 to 300ppm, user selectable FSD between 100 and 1000ppm (100 ppm resolution), includes nylon weather protection

SPXCDASMNX

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes nitrogen dioxide EC sensor cartridge 0 to 10ppm, user selectable FSD between 10 and 50ppm (5 ppm resolution), includes nylon weather protection

Part Number

Description

SPXCDASMG1

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes hydrogen EC sensor cartridge 0 to 1000ppm, includes nylon weather protection

SPXCDASMB1

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes infrared carbon dioxide sensor cartridge 0 to 2.0% v/v, includes nylon weather protection

SPXCDASMB2

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes infrared carbon dioxide sensor cartridge 0 to 5.0% v/v, includes nylon weather protection

ATEX/IECEx/Asian Approvals (LM25)

Part Number

Description

SPXCDALMFX

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes catalytic sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDALMRX

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes infrared methane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDALMPX

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes infrared propane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDALMO1

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes oxygen EC sensor cartridge 0 to 25% v/v, includes nylon weather protection

SPXCDALMHX

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes hydrogen sulfide EC sensor cartridge 0 to 50ppm, user selectable FSD between 10 and 100ppm (1 ppm resolution), includes nylon weather protection

SPXCDALMCX

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes carbon monoxide EC sensor cartridge 0 to 300ppm, user selectable FSD between 100 and 1000ppm (100 ppm resolution), includes nylon weather protection

SPXCDALMNX

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes nitrogen dioxide EC sensor cartridge 0 to 10ppm, user selectable FSD between 10 and 50ppm (5 ppm resolution), includes nylon weather protection

SPXCDALMG1

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes hydrogen EC sensor cartridge 0 to 1000ppm, includes nylon weather protection

SPXCDALMB1

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes infrared carbon dioxide sensor cartridge 0 to 2.0% v/v, includes nylon weather protection

SPXCDALMB2

XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes infrared carbon dioxide sensor cartridge 0 to 5.0% v/v, includes nylon weather protection

UL/c-UL/INMETRO Approvals (316SS)

Part Number

Description

SPXCDUSNFX

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes catalytic sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDUSNRX

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes infrared methane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDUSNPX

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes infrared propane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDUSNO1

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes oxygen EC sensor cartridge 0 to 25% v/v, includes nylon weather protection

SPXCDUSNHX

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes hydrogen sulfide EC sensor cartridge 0 to 50ppm, user selectable FSD between 10 and 100ppm (1 ppm resolution), includes nylon weather protection

SPXCDUSNCX

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes carbon monoxide EC sensor cartridge 0 to 300ppm, user selectable FSD between 100 and 1000ppm (100 ppm resolution), includes nylon weather protection

SPXCDUSNNX

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes nitrogen dioxide EC sensor cartridge 0 to 10ppm, user selectable FSD between 10 and 50ppm (5 ppm resolution), includes nylon weather protection

SPXCDUSNG1

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes hydrogen EC sensor cartridge 0 to 1000ppm, includes nylon weather protection

SPXCDUSNB1

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes infrared carbon dioxide sensor cartridge 0 to 2.0% v/v, includes nylon weather protection

SPXCDUSNB2

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes infrared carbon dioxide sensor cartridge 0 to 5.0% v/v, includes nylon weather protection

UL/c-UL/INMETRO Approvals (LM25)

Part Number

Description

SPXCDULNFX

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes catalytic sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDULNRX

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes infrared methane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDULNPX

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes infrared propane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDULNO1

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes oxygen EC sensor cartridge 0 to 25% v/v, includes nylon weather protection

SPXCDULNHX

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes hydrogen sulfide EC sensor cartridge 0 to 50ppm, user selectable FSD between 10 and 100ppm (1 ppm resolution), includes nylon weather protection

SPXCDULNCX

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes carbon monoxide EC sensor cartridge 0 to 300ppm, user selectable FSD between 100 and 1000ppm (100 ppm resolution), includes nylon weather protection

SPXCDULNNX

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes nitrogen dioxide EC sensor cartridge 0 to 10ppm, user selectable FSD between 10 and 50ppm (5 ppm resolution), includes nylon weather protection

Part Number

Description

SPXCDULNG1

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes hydrogen EC sensor cartridge 0 to 1000ppm, includes nylon weather protection

SPXCDULNB1

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes infrared carbon dioxide sensor cartridge 0 to 2.0% v/v, includes nylon weather protection

SPXCDULNB2

XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes infrared carbon dioxide sensor cartridge 0 to 5.0% v/v, includes nylon weather protection

ATEX/IECEx/Asian Approvals (316SS) with Modbus

Part Number

Description

SPXCDASMFXM

XCD Gas Detector,  4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes catalytic sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDASMRXM

XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes infrared methane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDASMPXM

XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes infrared propane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDASMO1M

XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes oxygen EC sensor cartridge 0 to 25% v/v, includes nylon weather protection

SPXCDASMHXM

XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes hydrogen sulfide EC sensor cartridge 0 to 50ppm, user selectable FSD between 10 and 100ppm (1 ppm resolution), includes nylon weather protection

SPXCDASMCXM

XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes carbon monoxide EC sensor cartridge 0 to 300ppm, user selectable FSD between 100 and 1000ppm (100 ppm resolution), includes nylon weather protection

SPXCDASMNXM

XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes nitrogen dioxide EC sensor cartridge 0 to 10ppm, user selectable FSD between 10 and 50ppm (5 ppm resolution), includes nylon weather protection

SPXCDASMG1M

XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes hydrogen EC sensor cartridge 0 to 1000ppm, includes nylon weather protection

SPXCDASMB1M

XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes infrared carbon dioxide sensor cartridge 0 to 2.0% v/v, includes nylon weather protection

SPXCDASMB2M

XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS, includes infrared carbon dioxide sensor cartridge 0 to 5.0% v/v, includes nylon weather protection

ATEX/IECEx/Asian Approvals (LM25) WITH Modbus

Part Number

Description

SPXCDALMFXM

XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes catalytic sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDALMRXM

XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes infrared methane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDALMPXM

XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes infrared propane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDALMO1M

XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes oxygen EC sensor cartridge 0 to 25% v/v, includes nylon weather protection

SPXCDALMHXM

XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes hydrogen sulfide EC sensor cartridge 0 to 50ppm, user selectable FSD between 10 and 100ppm (1 ppm resolution), includes nylon weather protection

SPXCDALMCXM

XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes carbon monoxide EC sensor cartridge 0 to 300ppm, user selectable FSD between 100 and 1000ppm (100 ppm resolution), includes nylon weather protection

SPXCDALMNXM

XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes nitrogen dioxide EC sensor cartridge 0 to 10ppm, user selectable FSD between 10 and 50ppm (5 ppm resolution), includes nylon weather protection

SPXCDALMG1M

XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes hydrogen EC sensor cartridge 0 to 1000ppm, includes nylon weather protection

SPXCDALMB1M

XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes infrared carbon dioxide sensor cartridge 0 to 2.0% v/v, includes nylon weather protection

SPXCDALMB2M

XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes infrared carbon dioxide sensor cartridge 0 to 5.0% v/v, includes nylon weather protection

UL/c-UL/INMETRO Approvals (316SS) with Modbus

Part Number

Description

SPXCDUSNFXM

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes catalytic sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDUSNRXM

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes infrared methane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDUSNPXM

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes infrared propane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDUSNO1M

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes oxygen EC sensor cartridge 0 to 25% v/v, includes nylon weather protection

SPXCDUSNHXM

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes hydrogen sulfide EC sensor cartridge 0 to 50ppm, user selectable FSD between 10 and 100ppm (1 ppm resolution), includes nylon weather protection

Part Number

Description

SPXCDUSNCXM

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes carbon monoxide EC sensor cartridge 0 to 300ppm, user selectable FSD between 100 and 1000ppm (100 ppm resolution), includes nylon weather protection

SPXCDUSNNXM

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes nitrogen dioxide EC sensor cartridge 0 to 10ppm, user selectable FSD between 10 and 50ppm (5 ppm resolution), includes nylon weather protection

SPXCDUSNG1M

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes hydrogen EC sensor cartridge 0 to 1000ppm, includes nylon weather protection

SPXCDUSNB1M

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes infrared carbon dioxide sensor cartridge 0 to 2.0% v/v, includes nylon weather protection

SPXCDUSNB2M

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes infrared carbon dioxide sensor cartridge 0 to 5.0% v/v, includes nylon weather protection

UL/c-UL/INMETRO Approvals (LM25) with Modbus

Part Number

Description

SPXCDULNFXM

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes catalytic sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDULNRXM

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes infrared methane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDULNPXM

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes infrared propane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather protection

SPXCDULNO1M

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes oxygen EC sensor cartridge 0 to 25% v/v, includes nylon weather protection

SPXCDULNHXM

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes hydrogen sulfide EC sensor cartridge 0 to 50ppm, user selectable FSD between 10 and 100ppm (1 ppm resolution), includes nylon weather protection

SPXCDULNCXM

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes carbon monoxide EC sensor cartridge 0 to 300ppm, user selectable FSD between 100 and 1000ppm (100 ppm resolution), includes nylon weather protection

SPXCDULNNXM

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes nitrogen dioxide EC sensor cartridge 0 to 10ppm, user selectable FSD between 10 and 50ppm (5 ppm resolution), includes nylon weather protection

SPXCDULNG1M

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes hydrogen EC sensor cartridge 0 to 1000ppm, includes nylon weather protection

SPXCDULNB1M

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes infrared carbon dioxide sensor cartridge 0 to 2.0% v/v, includes nylon weather protection

SPXCDULNB2M

XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes infrared carbon dioxide sensor cartridge 0 to 5.0% v/v, includes nylon weather protection

Honeywell Sensepoint XCD

Explosion-Proof Transmitters
Manufacturer: Honeywell
SKU: SPXCDASMFX [2]
£1,037.40 excl vat £1244.88 inc vat

Honeywell Sensepoint XCD

£1,037.40 excl vat £1244.88 inc vat
Picture of Worldwide Shipping

Worldwide Shipping

Place a purchase order, call or email to get an international shipping quote

Picture of Secure Online Purchasing

Secure Online Purchasing

SECURED BY SECTIGO (We do not accept AMEX)

Picture of Technical Support

Technical Support

Call or email to speak to a member of the technical team